Annex G: Case Studies - Operations
Operations |
||||||
---|---|---|---|---|---|---|
Topic |
Organisation |
Background |
Solution |
Results |
Awards |
Further Information |
Data Centre - Consolidation |
Aberdeen University, Robert Gordon University, Aberdeen College and Banff & Buchan College. |
Existing data centre facilities across all four institutions inadequate for future requirements, and unsustainable based on existing performance. |
Introduce a shared service approach to data centres, backed by energy efficient design (North East of Scotland Shared Data Centre). |
Carbon emissions reduced by 1,400 tonnes per annum (£250K per annum). |
|
|
St Andrews University. |
|
|
|
|
||
Operations |
||||||
Topic |
Organisation |
Background |
Solution |
Results |
Awards |
Further Information |
Bassetlaw District Council, Derbyshire. |
|
|
|
|
http://www.ukauthority.com/GreenICT/GreeningcouncilICTexamples/tabid/84/Default.aspx# |
Operations |
||||||
---|---|---|---|---|---|---|
Topic |
Organisation |
Background |
Solution |
Results |
Acknowledgements |
Further Information |
Data Centre - Virtualisation |
Sheffield Hallam University |
Excessive server count leading to space and outage problems. |
Replace 120 physical servers with 300 'virtual' servers. |
|
||
City of Leeds Council |
Data centre review resulted in excessive sever count. |
"Virtualise" 138 servers to 10 severs. |
Carbon emissions reduced by 767 tonnes per year. |
http://www.ukauthority.com/GreenICT/GreeningcouncilICTexamples/tabid/84/Default.aspx# |
||
Operations |
||||||
Topic |
Organisation |
Problem |
Solution |
Results |
Acknowledgements |
Further Information |
Data Centre - Cooling |
Fife Council |
Existing air conditioning in data centres is 10 years old and does not take into account significant developments in cooling over time. |
Redesign the layout of racks to reduce the amount of cooling required (switch to "cold isle" layouts and introduce a "free cooling" system to filter cold air from outside the building). |
Electricity bills reduced by £42,000 per annum (equating to carbon savings of 135 tonnes per year). |
http://www.gov.scot/Topics/Economy/digital/digitalservices/greenict |
|
Print Reduction |
Department For Work and Pensions |
Unsustainable printing costs and energy usage in printing. |
Introduce a managed print service - 30,000 legacy printers replaced with 8,200 energy star rated multifunctioning devices. |
Electricity consumption reduced by 63%. Financial savings via default double-sided printing. Help desk calls halved (and 90% reduction in the number of site visits by engineers to deal with faulty printers). |
Green ICT Awards Public Sector Project of the year, 2011. |
http://news.xerox.co.uk/news/green-it-award-goes-to-the-department-208377 |
Operations |
||||||
Topic |
Organisation |
Problem |
Solution |
Results |
Acknowledgements |
Further Information |
Desktop Video Conferencing Integration |
Natural Environment Research Council |
Unsustainable costs resulting from travel to meetings. High-level commitment at CEO level to reduce the CO 2 emissions. |
Installation of high definition desktop video conference equipment. |
Carbon emissions reduced by c. 15 tonnes (equating to £32,000 per annum) Reduction in travelling times (and thus staff costs) of equating to c. 1,400 hours per annum. |
Operations |
||||||
---|---|---|---|---|---|---|
Topic |
Organisation |
Problem |
Solution |
Results |
Acknowledgements |
Further Information |
Thin Client Terminals |
Queen Margaret University, Edinburgh |
Unsustainable running costs of existing desktop PC's. |
Replace standard desktops with 1,250 thin client terminals. |
|
|
Operations |
||||||
---|---|---|---|---|---|---|
Topic |
Organisation |
Problem |
Solution |
Results |
Acknowledgements |
Further Information |
Automated Power Management Employee Behaviour |
Staffordshire County Council |
Desk top PCs being left on overnight leading to unnecessary costs. |
Used software that:
|
Cost savings over £40,000 per year. |
http://www.ukauthority.com/GreenICT/GreeningcouncilICTexamples/tabid/84/Default.aspx |
|
University of Liverpool |
|